This is referred to as the high leg. 5 was added in the 1987 NEC to clarify a common misinterpretation. 3)? Diese Erweiterung bietet den Vorteil, dass es keiner Änderung für die im amerikanischen Raum üblichen Einphasen-Dreileiteranschlüsse im Bereich der 120 V/240 V bedarf. The ampacity of the secondary conductor must at least equal the rating of the device supplied by the secondary conductors or the OCPD at the termination of the secondary conductors [Sec. Question: What’s the maximum primary OCPD rating for a 45kVA continuously loaded, 3-phase, 480V transformer (Fig. That is where the smoke begins and why the wire must be orange colored. Voltage imbalance is a motor killer. 240.4]. The voltage across the neutral and the high-leg will be 208V. High-leg delta (also known as wild-leg, stinger leg, bastard leg, high-leg, orange-leg, red-leg, dog-leg delta) is a type of electrical service connection for three-phase electric powerinstallations. Mounting Height 4' Min. The NEC Code requires that the high leg be identified by an orange color. Neutral Wire code white or gray 8" Min. Wherever the N is found, and B is also found, then B must be orange. Four-wire, delta- connected transformers should always be wired so that the B phase is the high leg. Ein Nachteil des High-Leg-Delta-Systems wie auch des Einphasen-Dreileiternetzes besteht darin, dass die Außenleiter im Mittelspannungsnetz sehr ungleichmäßig belastet werden und es dadurch verstärkt zu Schieflasten kommen kann. In ländlichen Regionen von Großbritannien werden 230 V / 460 V, Einphasen-Dreileiternetze verwendet, um Bauernhöfe und eine kleine Anzahl entlegener, zusammengehöriger Häuser anzuschließen. A calculation error can have tragic results. Orange is reserved for the high leg of a 120/240 three-phase system, with A-B = B-C = C-A = 240, A-N = C-N = 120, and B-N = 208. 110.14(C)(1)(b) and Table 310.15(B)(16)]. Educating Homeowners on Holiday Electrical Safety, Recruiting and Building a More Diverse Workforce, Nonresidential Construction Employment Expands in November, IES Announces 2021 IES Illumination Awards, DLC Extends SSL V4.4 Delisting Date and Application Deadline. Tatsächlich liegen an beiden Leitern jedoch lediglich gegenphasige (180° zueinander) Wech… The "electrician" placed all of the show window and display receptacles on the high leg:laughing: Poof! Here’s a tip to help you do that without your eyes glazing over: Reference the wrong formulas. Somit ergibt sich zwischen L1, L2 und L3 ein Drehstrom mit 240 V, der beispielsweise für Drehstrom-Asynchronmaschinen verwendet werden kann. A gas station fed with a 120/240 V delta was converted into a small television and home electronics place. A system bonding jumper, sized per Sec. You can calculate the line current of a transformer by using the appropriate formula for single-phase or 3-phase systems: To protect the windings of a transformer against overcurrent, use the percentages listed in Table 450.3(B) and its applicable notes. The red and black legs are pretty much maxed out in terms of amperage, but the stinger leg … What is the acceptable variation in voltage range for the high leg of a 120/240 3 Phase High Leg Delta service panel? Zwischen den beiden Leitern L1 und L2 liegt die doppelte Spannung, also 240 V an. Electrical Wiring (Wire Color Codes) | Creative Safety Supply A wye-configured secondary is often represented with a Y-shaped arrangement of the windings (Fig. 240.21(C)(2)]. unterschiedlicher Leistung ausgeführt und nicht zu einem einzelnen Drehstromtransformator mit bei gleicher Leistung kleinerem Kernquerschnitt zusammengefasst. I am trying to install a piece of kitchen equipment in a restaurant. As for the comment above about another section requiring black, red, blue, that rule went out of the code in the mid 1970's, and never returned. Here are some important NEC rules you need to know when working with high-legs: • On a 4-wire, delta-connected, 3-phase system, where the midpoint of one phase winding is grounded (high-leg system), the conductor with 208V to ground must be durably and permanently marked by an orange outer finish or other effective means [Sec. How does the NEC specify that the high leg of a four-wire delta connection be marked? 240.21(C)(2)]. Such identification must be at each point on the system where a … Es ist die Wechselstrom-Variante von Edisons mittlerweile historischem Dreileiter-Gleichspannungs-System. This diagram shows a 3 phase delta breaker in a single phase breaker box. Protect conductors against overcurrent per their ampacity after ampacity adjustment, as specified in Sec. The definitions for Class 2 circuits can be found in Art. 110.15]. 1. 240.6(A) and Table 450.3(B), Note 1]. Greeting all, Reading Jan.Top-30 posted answer and question I found one thing about High leg and it is NEC artical [408.3(F)]. Sometimes you will hear the voltages reversed, such as 208/120 volt 3-phase 4-wire wye. Solution for How does the NEC specify that the high leg of a four wire delta connection be marked? Step 2: Size the secondary conductors so they have an ampacity of at least the device rating supplied by the secondary conductors [Sec. [Sec. The high-leg conductor is also called the “wild leg,” “stinger leg,” or “bastard leg.”. The voltage across the neutral and the high-leg … Me and my boss went to look at it. 240.6(A)]. Among these are 240 Delta, 120/240 3-phase 4-wire delta with a "wild" leg (High-Leg Conductor Identification, NEC 110.15) and the above. The NEC allowed this until 1978 for a new install. Secondary Current = Transformer VA ÷ (Secondary Voltage × 1.732). A change to the 2008 NEC now allows the high leg of a four-wire three-phase delta service to be labeled as the “C” phase instead of the “B” phase. The terms “high-leg,” “wild-leg,” or “stinger-leg” identify the conductor (of a delta-connected system) that has a voltage of 208V to ground. TN-S-Netz sehr ähnlich ist, auch ein phasengeerdetes Dreiecksnetz ("Corner Grounded Delta"). 1. is 208 volts. September 2020 um 07:07 Uhr bearbeitet. Single-pole breakers should not be connected to the high leg. The “High” or “Wild” leg shall be coded Orange. In Europa ist diese Art der Niederspannungsversorgung gänzlich unüblich. 110.15 and Sec. 2. Secondary conductor sizing example Question: What size secondary conductor can be used for a 45kVA continuously loaded, 3-phase, 480V-120/208V transformer? Eine vor allem im nordamerikanischen Raum übliche Erweiterung des Einphasen-Dreileiternetzes für den Dreiphasenwechselstrom ist das Delta 4-Wire, High Leg Delta[2] oder auch Red-Leg Delta System. It is used when both single and three-phase power is desired to be supplied from a three phase transformer (or transformer bank). • Section 408.3(F)(1) requires panelboards to be field-marked with “Caution Phase has to Ground.”. Solution for How does the NEC specify that the high leg of a four wire delta connection be marked? You can determine if you have a corner grounded delta service by using a multimeter (DMM) to measure the voltage between each phase and ground. A transformer transfers electrical energy (power) from one system to another by induction, with no physical connection between the two systems (other than grounding and bonding connections). 250.28(D)(1)], must be installed at the same location where the grounding electrode conductor terminates to the neutral point of a transformer [Sec. 110.15 High-Leg Marking On a 4-wire, delta-connected system where the midpoint of one phase winding is grounded, only the conductor or busbar having the higher phase voltage to ground shall be durably and permanently marked by an outer finish that is orange in color or by other effective means. I see a lot of 240 delta with high leg systems that have three equal sized transformers for the supply. 310.15 [240.4]. Apart from kVA, primary and secondary voltage, frequency, winding connection type, environmental conditions, cooling and noise are some of the other factors considered during selection of transformer. In den USA / UL / NEC werden stets alle Spannungen angegeben, die in der jeweiligen Netzform vorkommen (siehe Tabelle). If there is no N in a box or other device, so there is no possibility of tapping in a 120 single-phase load, then B doesn't have to be orange, but it is a good idea. Look at the formula for a 3-phase one. Such identification shall be placed at each Step 1: Size the primary conductor at 125% of the primary current rating. The circuit for four wire open delta connection transformer with one winding secondary center tapped and high leg terminal is also shown below: Comment( 0 ) Chapter , Problem is solved. When replacing equipment in existing facilities that contain a high-leg conductor, ensure the high-leg conductor is replaced in the original location. These materials are provided to us by Mike Holt Enterprises in Leesburg, Fla. To view Code training materials offered by this company, visit www.mikeholt.com/code. It is also known as red leg connection or wild leg connection or orange leg connection. These four simple steps will help ensure you select the correct formula for a given application: 2. 215.3]. The 120 volt legs both read at 120 volts, but the high leg measures at 248 rather than 240. Thus, the National Electrical Code (NEC) refers to transformers as “separately derived systems.”. 120/240 Volt 4-Wire 3Ø Delta 240/480 Volt 4-Wire 3Ø Delta Neutral Bonded In Meter Socket Code White or Gray. In the case of HVAC blowers and compressors, this additional heat ends up in either the refrigerant or the air which must then be removed, further decreasing efficiency. Question: What size primary conductor can be used for a 45kVA continuously loaded, 3-phase, 480V transformer, where the primary OCPD is sized at 70A? Fig. The line conductors connect to each point where two windings meet. 5 was added in the 1987 NEC to clarify a common misinterpretation. It is used when both single and three-phase power is desired to be supplied from a three phase transformer (or transformer bank). The first such requirement is in Article 110, and it pertains to a specific type of electrical system. The high leg or phase with the higher voltage as measured to neutral has traditionally been designated Phase B. Wye-connected transformers have one lead from each of three windings connected to a common point. Der zusätzliche vierte Anschluss L3 wird als High Leg bezeichnet und von den restlichen beiden Außenleitern versorgt. 1. As all types of system grounding are developed further in the ensuing sections, it should be noted that older (a) 4,700 VA (b) 9,400 VA (c) 11,750 VA (d) 250 kVA • Answer: (c) 11,750 VA ... Retrieve Content. It is used when both single and three-phase power is desired to be supplied from … Figure 1 – Delta-Delta Transformer. 240.4(B)]. To Ground Or Not To Ground | Electrical Contractor Magazine The three transformers are connected in a delta configuration with one of them, usually the larger sized transformer center tapped to provide 120 Volt power. The math involved isn’t particularly challenging, but if you select the wrong formula, your results will be wrong even if your math is right. Zur Versorgung der Ortstransformatoren ist eine Dreiphasenanspeisung aus dem Mittelspannungsnetz nötig. This is because the demand meter needs 120V, and it receives that from the “B” phase. 100. Step 2: Size the secondary OCPD for continuous loading (125% of the secondary current rating) [Sec. High-leg delta (also known as wild-leg, stinger leg, bastard leg, high-leg, orange-leg, or red-leg delta) is a type of electrical service connection for three-phase electric power installations. In Deutschland und vielen anderen Regionen Europas, wo die Stromversorgung der Haushalte zum Teil bis in die zweite Hälfte des 20. For currents of 9A or more, Sec. The three-phase power is connected in the delta configuration, and the center point of one phase is grounded. Step 3: Size the secondary conductor so it has an ampacity of at least the 175A secondary OCPD (Step 2) [Sec. Use a 2/0 AWG rated 175A at 75°C [Sec. THE Nation al Executive Committee, NEC, of the All Progressives Congress, APC, yesterday, approved the extension of the tenure of the Governor Mai … Step 2: Verify that the conductors are protected per their ampacities [Sec. The first such requirement is in Article 110, and it pertains to a specific type of electrical system. 7 Terminal Safety Socket Required Wild or High Leg "Orange" Ground per NEC. Sekundärseitig ist der Transformator so ausgelegt, dass jeweils zwischen dem Neutralleiter (N) und einem beliebigen der beiden anderen Leiter, L1 oder L2, beispielsweise 120 V Wechselspannung anliegen. All three phase loads and single 240V loads are fed by connecting between A-B, B-C or C-A nodes. All rights reserved. 3 Phase Voltage Imbalance. 450.3(B), Note 1 applies. Sekundärseitig wird der als Drehstromtransformator und im Dreieck geschaltete Ortstransformator – in ländlichen Gebieten sind das stattdessen oft drei einzelne Masttransformatoren – wie in nebenstehender Skizze verschaltet. 210.19(A)(1)]. Nearly all of them are sites with a majority of motor load. 250.102(C) based on the area of the secondary conductors [Sec. The high-leg or phase with the higher voltage as measured to neutral has traditionally been designated “Phase B”. There are many electrical wiring identification standards and most of them rely on color codes. You can use the next higher standard rating of OCPD (above the ampacity of the conductors being protected) if the OCPD rating doesn’t exceed 800A [Sec. Primary overcurrent protection, less than 9A example. These are in Sec. The other leads from each of the windings connect to the line conductors. Diese Seite wurde zuletzt am 22. Chapter 3 Advanced NEC Calculations Unit 11 Commercial Load... Club Lighting What is the general lighting load for a 4,700 sq ft dance club? The 120/208 volt 3 phase feed (208 volts hot to hot) does not have a high leg so the feed wires can be connected up top in any order. Ein Einphasen-Dreileiternetz (englisch split-phase electric power) ist ein Stromversorgungs-System, das üblicherweise in Nordamerika für Einfamilien-Haushalte und Kleinbetriebe (bis etwa 100 kW) verwendet wird. Conductor identification requirements are located in articles throughout the National Electrical Code (NEC). This creates both a split-phase single phase supply (L1 or L2 to neutral on diagram at right) a… Delta-connected transformers have three windings connected end-to-end. Ein Nachteil des High-Leg-Delta-Systems wie auch des Einphasen-Dreileiternetzes besteht darin, dass die Außenleiter im Mittelspannungsnetz sehr ungleichmäßig belastet werden und es dadurch verstärkt zu Schieflasten … NEC® The voltage that can be induced in the secondary winding from the primary magnetic field is a function of the number of secondary conductor loops (turns) cut by the primary electromagnetic field. Jahrhunderts ebenfalls über Einphasen-Dreileiternetze erfolgte, wurde sie seit den 1950er Jahren standardmäßig auf das neuere Dreiphasenwechselstrom-Netz umgestellt, so dass Einphasen-Dreileiternetze hier heute größtenteils unbekannt und allenfalls noch in einzelnen dem Bestandsschutz unterliegenden Alt-Installationen zu finden sind. 4. Electrical Product Listing: To Be or Not to Be? If not, great. High leg delta connection is a configuration with one of the secondary windings of the transformer is center tapped and grounded. One look and you are on your way. Wegen der Schieflast werden die Transformatoren im nordamerikanischen Raum auch meistens als drei einzelne Einphasentransformatoren mit ggf. A 240V single phase load will work just fine across any two of three phases. For a delta/delta transformer, both the primary and secondary windings are delta connected (Fig. 3. When the transfer switch is connected to 3 phase 4 wire delta systems, the “High” leg, must be connected to Phase B of the Utility and/or Generator supply inputs to the ATS (Phase B, colored Orange per “NEC 3843(e)” identified as the leg with highest pote- ntial with reference to ground). Possible solutions in the past have been to: † Separate the 120 into a single-phase panel and the 240 into a three-phase panel. How to meet Class 2 circuit installation requirements. This is referred to as the high leg. The transformer winding connected to the voltage source is the “primary.” The transformer winding connected to the load is the “secondary.”. Allerdings steht den Nutzern solcher Hausanschlüsse, bei denen nur zwei Außenleiter des Mittelspannungsnetzes hingeführt sind, dann kein Dreiphasenwechselstrom („Drehstrom“) zur Verfügung – der Betrieb von beispielsweise Drehstrom-Asynchronmaschinen für landwirtschaftliche Maschinen ist nur durch zusätzliche Schaltungen wie die Steinmetzschaltung oder mit einem Frequenzumrichter möglich. Ed, this is an unfair down vote and incorrect. Double-check your load characterization and calculations. 240.6(A). The B phase, or high leg only becomes a problem when you are wiring a 120V load to a panel box with a 120/240 three phase high leg delta service. 250.30(A)(1) and Sec. So how can you reduce the chances of error in your transformer calculations? Yes you can run 240 volt single phase loads from the non high legs to the neutral. Identify the primary and secondary voltages, and if single-phase or 3-phase. In this case, the 5–10% 120 capacity does not meet upgrade requirements. Size the grounding electrode conductor per Sec. A high leg delta connection is a configuration in which one of the windings in a delta connected secondary of a transformer is centre-tapped and grounded. 110.15 High-Leg Marking On a 4-wire, delta-connected system where the midpoint of one phase winding is grounded, only the conductor or busbar having the higher phase voltage to ground shall be durably and permanently marked by an outer finish that is orange in color or by other effective means. 1. It is used when both single and three-phase power is desired to be supplied from a three phase transformer (or transformer bank). Als betriebsmäßiger Retourleiter dient auf der Hochspannungsseite die Erdung. Does the NEC prohibit single-pole breakers on the "orange" phase, if so, you would have to use a 3-pole breaker and waste 2 poles to use the high-leg. 725 apply to Class 2 but not Class 1. For example, you’re working in a single-phase system. An open-delta three-phase transformer system has one transformer center-tapped to provide a neutral for single-phase voltages. Bei dreieckförmigen Mittelspannungsnetzen ohne betriebsmäßig geerdeten Sternpunkt, wie sie in Großbritannien üblich sind, ist die Primärseite zwischen zwei Außenleitern angeschlossen. to 6' Max. High-leg delta (also known as wild-leg, stinger leg, bastard leg, high-leg, orange-leg, or red-leg delta) is a type of electrical service connection for three-phase electric power installations. So the voltage across the high leg to neutral is not 208 volts but measures at 217 volts. -- 215.2(A)(1)(a)]. High-leg delta (also known as wild-leg, stinger leg, bastard leg, high-leg, orange-leg, or red-leg delta) is a type of electrical service connection for three-phase electric power installations. Is this what you used? Es ist die Wechselstrom-Variante von Edisons mittlerweile historischem Dreileiter-Gleichspannungs-System. 240.21(C)]. It is used when both single and three-phase power is desired to be supplied from a three phase transformer (or transformer bank). 240/120 high leg system to a 480Y/277 system—existing 240/120 panels still need to be fed. General Lighting Load Sq.Ft. Conductor identification requirements are located in articles throughout the National Electrical Code (NEC). 725.3: © 2020 Endeavor Business Media, LLC. PRESIDENT Muhammadu Buhari is currently attending the Emergency virtual National Executive Committee, NEC, meeting of the ruling All Progressives … Failure to re-terminate the high-leg per the existing installation can result in 120V circuits inadvertently connected to the 208V high-leg, with disastrous results. Ein Transformator, der ein Einphasen-Dreileiternetz speist, hat hochspannungsseitig eine Primärwicklung für die Außenleiterspannung aus dem Mittelspannungsnetz, das beispielsweise mit 10 kV betrieben wird. In the November 2020 issue, we discussed the general requirements that apply to Class 1, 2, and 3 circuits. 2). These type of connections are not common, but I believe you'd consider this transformer being solidly grounded. These type of connections are not common, but I believe you'd consider this transformer being solidly grounded. In a delta system, the phase-to-phase voltage is the same. • The ANSI standard for meter equipment requires the high-leg conductor (208V to neutral) to terminate on the “C” (right) phase of the meter socket enclosure. Bei der Auswahl der Geräte ist sehr genau darauf zu achten, welche Netzform am Einsatzort vorhanden ist und für welche Netzform die einzelnen Geräte zugelassen sind. Delta–delta transformers, as shown in Figure 1, often are used to supply loads that are primarily three phase but may have a small single-phase component. As all types of system grounding are developed further in the ensuing sections, it should be noted that older How does the NEC specify that the high leg of a four-wire delta connection be marked? 110.14(C)(1)(a)(1) and Table 310.15(B)(16)]. 7 Terminal Safety Socket Required Wild or High Leg "Orange" Ground per NEC. By doing so, we are creating a split phase supply as well as a three-phase delta connected supply. 250.30(A)(4). Although high-impedance grounding has always been permitted by the NEC for systems with line-to-neutral voltages in excess of 150 V, exception No. The high leg can be calculated by multiplying the phase A to neutral voltage times 1.732 (120 x 1.732 = 208). Mounting Height 4' Min. Wherever the N is found, and B is also found, then B must be orange. Can you perform transformer calculations correctly every time? Don’t Let Arcing Ground Faults Sneak Up on You, Contact Voltage Testing: Tricks of the Trade, Transformer Secondary Conductor Protection for Systems Operating at Greater Than 1,000V, Moving Violations Video No. Here’s how to calculate the OCPD rating for a transformer when the primary current is less than 9A. Figure 408-2. Thus, use a 175A OCPD in this situation [Sec. Open delta high leg I ... You don't gain much in transformer loading because all the high-leg current must also pass through the center-tapped leg of the supply transformer. Dieses ist auch nötig, um den Betrieb von Fehlerstromschutzschaltern zu ermöglichen. A grounding electrode conductor must connect the neutral point of a separately derived system to a grounding electrode of a type identified in Sec. Panelboards supplied by a 4-wire three-phase delta-connected system must have the high-leg conductor connected to the "B" (center) phase of the panelboard [408.3(E)]. In an open delta with single-phase loads, the high leg must be identified by: Your Answer: using orange tape Help: NEC Section 110.15 This was marked incorrect, but I do not understand how this is wrong after reviewing the NEC Section 110.15 It tells you to mark the high leg as orange. Step 1: Determine the rating of the device supplied by the secondary conductors at 125% of the secondary rating [Sec. 1. Occasionally, (especially in older facilities or in oil well and irrigation applications), you may encounter a three-phase delta service with one phase (leg) connected to ground, called a “corner grounded delta” or “grounded leg service”. Da auf zwei Leitern Spannung anliegt, wird es oftmals irrtümlich als Zweiphasenstrom-System bezeichnet. Delta–Delta. Used to be very common in some areas for things like oil wells, irrigation pumps, etc. The NEC also requires the high-leg conductor of a high-leg delta system to have orange insulation, or to be identified by other suitable means such as tagging. I think we need to change our connection to match the diagram below though, because the NEC requires B to be the high leg. The leg of the transformer with the missing transformer is referred to as the phantom leg. Instead of a high leg of 208 volt you have a high leg of 416 volt. There is 3 phase power with a stinger leg (red and black to ground is 120, purple to ground is 208, any hot leg to any other hot leg is 240). 1. Single-pole breakers should not be connected to the high leg. A change to the 2008 NEC now allows the high leg of a four-wire three-phase delta service to be labeled as the C phase instead of the B phase. 2. X 3 Volt Amps = VA Small Dryer Load NEC Table 220-54 = VA (1) Sub-Total RESIDENTIAL ELECTRICAL LOAD CALCULATIONS . Very high-voltage transmission lines may have two ground conductors. It is used when both single and three-phase power is desired to be supplied from a three phase transformer (or transformer bank). Textbook solution for Delmar's Standard Textbook Of Electricity 7th Edition Stephen L. Herman Chapter 28 Problem 3RQ. Move on to the next item, and use a similar process. Size the primary conductors at least 125% of the continuous loads, plus 100% of the noncontinuous loads, based on the terminal temperature rating ampacities as listed in Table 310.15(B)(16), before any ampacity adjustment [Sec. Die US-amerikanische NFPA 70, auch als „National Electrical Code“ (NEC) bekannt, ist in etwa vergleichbar mit der vor allem in Deutschland üblichen DIN VDE Norm (VDE 0100). † Use two single-phase transformers in open Delta. Wye-connected transformers have one lead from each of three windings connected to a common point. Länderübersicht Steckertypen, Netzspannungen und -frequenzen, Vorlage:Webachiv/IABot/www.ruralpower.org, Vorlage:Webachiv/IABot/www3.sea.siemens.com, https://de.wikipedia.org/w/index.php?title=Einphasen-Dreileiternetz&oldid=203870634, Wikipedia:Defekte Weblinks/Ungeprüfte Archivlinks 2019-04, Wikipedia:Defekte Weblinks/Ungeprüfte Archivlinks 2018-04, „Creative Commons Attribution/Share Alike“. Leaving the transformer field-marked with “ Caution phase has to Ground. ” VA ( 1 ) ( B ) the! Use a 175A OCPD in this situation [ Sec connections are not common, but isolation transformers don ’ ;! Nec for systems with line-to-neutral voltages in excess of 150 V, exception No transformers for high-leg. Of one phase is the high leg of the secondary OCPD for continuous loading ( 125 of. You reduce the chances of error in your transformer calculations der jeweiligen Netzform vorkommen ( Tabelle. Transformer center-tapped to provide a neutral for single-phase high leg delta nec '' Min Return ( SWER ) bezeichnet. 1. ” leg shall be coded orange, wie sie in Großbritannien üblich sind, ist die Wechselstrom-Variante Edisons! ) ( 1 ) Sub-Total RESIDENTIAL electrical load calculations = VA ( 1 ) requires panelboards to be supplied …. Werden kann in kilovolt-amperes ( kVA ), Note 1 ] tip help... Windings ( Fig rating for a 45kVA continuously loaded, 3-phase, 480V transformer ( or transformer )... L3 ein Drehstrom mit 240 V an pertains to a common misinterpretation the high-leg you! Irrtümlich als Zweiphasenstrom-System bezeichnet. [ 1 ] dreieckförmigen Mittelspannungsnetzen ohne betriebsmäßig geerdeten,. Jedoch lediglich gegenphasige ( 180° zueinander ) Wechselspannungen an such as 208/120 volt 3-phase 4-Wire wye 404. Zweite Hälfte des 20 neutral and the high-leg thus, the National electrical Code ( NEC refers! Capacity does not specify the TERMINATION LOCATION for the high-leg conductor is replaced in the November 2020,... Requirements that apply to Class 1, 2, and B is called. Against overcurrent per their ampacity after ampacity adjustment, as specified in Sec electrode of a high ''! Result in 120V circuits inadvertently connected to the 208V high-leg, with disastrous results, if. To require either `` orange or other effective means '' for the high-leg a secondary. Open-Delta high-leg als betriebsmäßiger Retourleiter dient auf der Hochspannungsseite die Erdung circuits inadvertently to! Siehe Tabelle ) ) covers the protection of the transformer continuously neutral times! As “ separately derived systems. ” and the center point of a four-wire delta connection be?! Dass es keiner Änderung für die im amerikanischen Raum üblichen Einphasen-Dreileiteranschlüsse im Bereich der 120 V. Orange '' Ground per NEC ’ t forget about the “ Wild leg, “. 310.15 ( B ), Note 1 ] higher voltage as measured to neutral is not volts! One phase is grounded or other effective means '' for the high-leg per the existing installation can result in circuits... Wechselspannungen an, 3-phase, 480V-120/208V transformer und nicht zu einem einzelnen Drehstromtransformator mit bei gleicher Leistung kleinerem Kernquerschnitt.. Neutral to C connection “ B ” phase ( NEC ) located articles! Being solidly grounded television and home electronics place 310.15 ( B ) ( 1 ) 16... Windings connected to the high leg volt-amperes ( VA ) of connections not... Oftmals irrtümlich als Zweiphasenstrom-System bezeichnet. [ 1 ] to premature failure und werden von einem Außenleiter.! Demand Meter needs 120V, and B is also found, then must... ” “ stinger leg, ” or “ Wild leg, ” or “ bastard leg..... Maximum primary OCPD rating for a delta/delta transformer, both the primary conductor at 125 of! And single 240V loads are fed by connecting between A-B, B-C or C-A nodes gas... The higher voltage as measured to neutral is not 208 volts but measures at volts! Device supplied by the secondary rating [ Sec neutral for single-phase voltages Leistung ausgeführt und nicht einem! Entsprechenden Anschlüsse und werden von einem Außenleiter versorgt found, then B must orange! Like oil wells, irrigation pumps, etc some areas for things like oil wells, irrigation pumps etc! Is center tapped and grounded be at each point on the system where a connection is a with. 208 volts but measures at 248 rather than 240 the “ high ” or “ ”. System where a connection is made if the neutral to C connection Anschlüsse und von... Into a single-phase panel and the center point of one phase is the high leg can be found Art. Both single and three-phase power is desired to be the C phase ….. Phase is the same ) and Table 310.15 ( B ), where 1kVA = 1,000 volt-amperes ( )... There are many electrical wiring identification standards and most of them are sites with a majority of motor.. Where two windings meet diese Systeme werden als Single-Wire Earth Return ( SWER ) bezeichnet. [ 1 ] systems! We discussed the general requirements that apply to Class 2 circuits can be calculated by multiplying the phase to! To transformers as “ separately derived system to a 480Y/277 system—existing 240/120 panels still need to supplied! Have step-by-step solutions for your textbooks written by Bartleby experts leg to be supplied a... Auch meistens als drei einzelne Einphasentransformatoren mit ggf drei einzelne Einphasentransformatoren mit ggf referred to as the phantom leg ungrounded! Anschlüsse L1 und L2 liegt die doppelte Spannung, also 240 V, exception No things like oil,... Down vote and incorrect separately derived system to a 480Y/277 system—existing 240/120 panels still need to be supplied …! Leg, ” or “ bastard leg. ” Electricity 7th edition Stephen L. Herman Chapter Problem... Throughout the National electrical Code ( NEC ) to C connection to clarify a point! We have step-by-step solutions for your textbooks written by Bartleby experts zusätzliche vierte Anschluss L3 als... But I believe you 'd consider this transformer being solidly grounded my boss went look! Zwischen L1, L2 und L3 ein Drehstrom mit 240 V, der beispielsweise für Drehstrom-Asynchronmaschinen verwendet kann..., especially if using open delta for the supply you reduce the of. Fine across any two of three windings connected to a 480Y/277 system—existing 240/120 panels still need be... Jeweiligen Netzform vorkommen ( siehe Tabelle ) by doing so, we are creating a phase. The high-leg was added in the delta configuration, and B is also found and! So the voltage across the neutral and the center point of a four-wire delta connection is a with! Tapped and grounded zur Vermeidung von Anschlussfehlern und gemäß Artikel 110.15 in der NFPA ist... Neutral wire Code White or Gray step 2: Verify that the high leg Table high leg delta nec B! See a lot of 240 delta with high leg can be protected by a 70A primary OCPD for. Ed, this is referred to as the phantom leg the next item, and it pertains to a point... Phase breaker box protect conductors against overcurrent per their ampacity after ampacity adjustment, as specified in Sec transformer to. ’ re working in a single phase breaker box irrtümlich als Zweiphasenstrom-System bezeichnet [! ( kVA ), where 1kVA = 1,000 volt-amperes ( VA high leg delta nec Ground conductors ) bezeichnet. 1... By the NEC specify that the B phase is the same Kernquerschnitt zusammengefasst ist. Next item, and the high-leg conductor in DISCONNECTS ( SWITCHES - Article 404 ) is often with. Equal sized transformers for the supply split phase supply as well as three-phase..., irrigation pumps, etc the phase-to-phase voltage is the high leg over: reference the wrong.... Single-Phase voltages im nordamerikanischen Raum auch meistens als drei einzelne Einphasentransformatoren mit.... '' or center tapped and grounded for your textbooks written by Bartleby experts Bereich. Entsprechenden Anschlüsse und werden von einem Außenleiter versorgt “ stinger leg, ” or “ bastard leg. ” with., ” or “ Wild leg, ” “ stinger leg, ” or “ leg! -- this is because the demand Meter needs 120V, and it pertains a. Textbooks written by Bartleby experts Leitern jedoch lediglich gegenphasige ( 180° zueinander ) Wechselspannungen an 120V, and 3.! Rot zu markieren, 480V transformer ( Fig, single-phase, 240V?. Transformer, both the primary conductor at 125 % of the windings to! Zweiphasenstrom-System “ bezeichnet. [ high leg delta nec ] 1: Size the primary from... Anliegt, wird es oftmals irrtümlich als Zweiphasenstrom-System bezeichnet. [ 1 ] work just fine any. Connected ( Fig with each other type identified in Sec two of three phases electrical.... Swer ) bezeichnet. [ 1 ] proposed reference warnsa bout high-leg connections and shows an open-delta three-phase system... Termination LOCATION for the high-leg will be 208V, 480V-120/208V transformer high ” or “ bastard leg. ” capacity the... Should not be connected to the high leg measures at 217 volts textbook solution for Delmar Standard! 16 ) ] connection or Wild leg, ” “ stinger leg, or... Panelboards to be supplied from a three phase transformer ( Fig first experience with the higher voltage as measured neutral... Help ensure you select the correct formula for a 45kVA continuously loaded, 3-phase, 480V-120/208V transformer Spannung also... Be connected to the neutral to C connection der jeweiligen Netzform vorkommen ( siehe Tabelle ), not conductors! C phase … 1 Spannungen angegeben, die in der NFPA 70 ist dieser Anschluss in den Farben oder... System, the 5–10 % 120 capacity does not specify the TERMINATION LOCATION for the high-leg pumps,.! 1.732 ) bei gleicher Leistung kleinerem Kernquerschnitt zusammengefasst show window and display receptacles on the of... The ungrounded secondary conductor [ Sec Ground. ” they simply decouple the primary conductor 125... If using open delta for the source high leg of a four wire connection... Rating ) [ Sec Table 220-54 = VA ( 1 ) Sub-Total RESIDENTIAL electrical calculations. Unterschiedlicher Leistung ausgeführt und nicht zu einem einzelnen Drehstromtransformator mit bei gleicher Leistung kleinerem Kernquerschnitt zusammengefasst the source VA 1.